groundranger
Recent · latest filing Oct 2025Commercial

8161 Moberly Ln

Dallas, TX 75227

Electrical panel replacement at 8161 Moberly Ln

Commercial electrical permits filed in October 2025 indicate replacement of the building’s 4,000-amp main distribution panel with a 2,000-amp panel and installation of a 1,200-amp disconnect. The City of Dallas records list permits COM-ELC-25-002565, filed October 6, and COM-ELC-25-002611, filed October 23.

Summarized from City of Dallas records · updated Oct 23, 2025

Projects
3
3 filings
Latest filing
Oct 23, 2025
since Dec 9, 2020
Largest scope
—
Listed value
$696
partial · often understated

Permit & project history

3 projects
  1. Replace old/outdated 4000a main distribution panel (mdp-1) which feed the whole building with a new 2000a main distribution panel, install a 1200a service rated fusible disconnect on the right side of the transition box (wire from transformer connected to copper buss which feed the mdp-1 inside. disconnect 4 parallel sets of 1000 kcmil from the transition box and install to the top of the 1200a disconnect and run 4 parallel sets of 400 kcmil from the load side of the 1200a disconnect to the copper buss in the transition box to feed the new 2000a mdp -1. we will need the power disconnected from the transformer in different weekends. first weekend will install 1200a disconnect and temporary run power from the load side of the disconnect to power up existing mdp-2, circuits from mdp-1 will temporarily be relocated to mdp-2 which will feed the building temporary while during the week the old mdp-1 will be removed and the new mdp-1 be installed. the second shut down of the transformer will permanently connect the load side of the 1200a disconnect to the new mdp-1 and circuits will be transferred back to the new mdp-1“

    Replace old/outdated 4000a main distribution panel (mdp-1) which feed the whole building with a new 2000a main distribution panel, install a 1200a service rated fusible disconnect on the right side of the transition box (wire from transformer connected to copper buss which feed the mdp-1 inside. disconnect 4 parallel sets of 1000 kcmil from the transition box and install to the top of the 1200a disconnect and run 4 parallel sets of 400 kcmil from the load side of the 1200a disconnect to the copper buss in the transition box to feed the new 2000a mdp -1. we will need the power disconnected from the transformer in different weekends. first weekend will install 1200a disconnect and temporary run power from the load side of the disconnect to power up existing mdp-2, circuits from mdp-1 will temporarily be relocated to mdp-2 which will feed the building temporary while during the week the old mdp-1 will be removed and the new mdp-1 be installed. the second shut down of the transformer will permanently connect the load side of the 1200a disconnect to the new mdp-1 and circuits will be transferred back to the new mdp-1“

    City of Dallas permitCommercial Electrical Permit
    Record
    COM-ELC-25-002611
    Tenant / owner
    Pro
    Contractor
    Pro
    Contact
    Pro
  2. Replace old/outdated 4000a main distribution panel with a new 2000a main distribution panel, install a 1200a service rated fusible disconnect on the right side of the transition box (copper wire to copper buss). disconnect 4 parallel sets of 1000 mcm from copper buss and insert to top of 1200a disconnect and run 4 parallel sets of 400 mcm from the load side of the disconnect to the copper buss

    Replace old/outdated 4000a main distribution panel with a new 2000a main distribution panel, install a 1200a service rated fusible disconnect on the right side of the transition box (copper wire to copper buss). disconnect 4 parallel sets of 1000 mcm from copper buss and insert to top of 1200a disconnect and run 4 parallel sets of 400 mcm from the load side of the disconnect to the copper buss

    City of Dallas permitCommercial Electrical Permit
    Record
    COM-ELC-25-002565
    Tenant / owner
    Pro
    Contractor
    Pro
    Contact
    Pro
  3. Install fire sprinkelr system & underground fireline

    Install fire sprinkelr system & underground fireline

    City of Dallas permitFire Sprinkler (Major Work) (FI) Commercial Alteration$696
    Record
    2011181105
    Tenant / owner
    Pro
    Contractor
    Pro
    Contact
    Pro

Sources: City of Dallas

Questions about 8161 Moberly Ln

What work is planned at 8161 Moberly Ln in Dallas?

City of Dallas permits indicate replacement of an outdated main electrical distribution panel and installation of a 1,200-amp disconnect.

When were permits filed for electrical work at 8161 Moberly Ln?

The City of Dallas filed commercial electrical permits COM-ELC-25-002565 on October 6, 2025, and COM-ELC-25-002611 on October 23, 2025.

Is a new building being constructed at 8161 Moberly Ln?

The records provided describe electrical equipment replacement, not construction of a new building.

What size electrical panel is being installed at 8161 Moberly Ln?

The permits describe replacing the existing 4,000-amp main distribution panel with a new 2,000-amp panel.

What is the 1,200-amp disconnect for at 8161 Moberly Ln?

The permit descriptions indicate it will connect the electrical service to the new main distribution panel.

Also being built nearby

All of 75227

More warehouses & industrial in 75227.

Get alerts for 8161 Moberly Ln